Low Voltage Back
 

 

 

 

 
 
Home  >> Products >> Low Voltage >> RCD/RCCB/RCBO & so on >> SGLD Series Automatic Change-over Switch
 
   
 
1. Application
 
SGLD automatic change-over switch(ATSE) integrates switch and logic control, thus it is not necessary to provide external controller. This truly electromechanically integrated automatic change-over switch has the following functions such as voltage detection, frequency detection, communication interface, electrical and mechanical interlocking etc.,so, automatic control, electrical remote control and emergency manual control can be performed.
The operation is carried out through the logic control board, which gives various commands to control the motor and gear-box. the motor drives the accelerator which can take switch-spring power accmulating and instantaneous release, swiftly turns making and breaking the circuit or makes circuit switching, the visible operation status can help you to perform safe separation, increasing extremely the various electrical and mechanical performance.
Which the shell of switch SGLD is made of different materials: the control section is made of metal, but the switching section is made of glass-fibre unsaturated polyester resin, having stronger dielectric property and protective capability as well as safe operation performance.
This kind of switch is suitable for the automatic changeover of the main power source and the secondary power source of the power supply system of the automatic change-over and safe separation of the 2 sets of load-equipment. This kind of switch has a beautiful, novel and simple structure, a small volume but complete functions, being the best choice among congeneric of products.
SGLD series had been already passed the detection of EMC.

 
2. Specification
 
Conventional thermal current lth(A) 100A 160A
Rated current In(A)
20A 40A 63A 80A 100A 125A 160A
Rated impulse withstand voltage Ui(V)
500 500 500 500 500 500 500
Dielectric strength(V)
5000 5000 5000 5000 5000 5000 5000
Rated surge-resistant voltage Uimp kV(installed category IV)
8 8 8 8 8 8 8
Rated working current
380V
AC-31
20 40 63 80 100 125 160
AC-33
20 32 40 63 80 125 160
AC-35
20 40 63 80 100 125 160
220V
DC-31
20 40 63 80 100 125 160
DC-33
20 32 40 63 80 100 125
DC-35
20 40 63 80 100 125 160
Moter power P(380V) kW
10 20 25 30 32 63 80
Rated short-time withstand current(kA Rms)0.1S/1.0S
9/5 9/5 9/5 9/5 9/5 20/10 20/10
Rated breaking capbility(A Rms)AC33 380V
160 320 500 640 800 1000 1000
Rated making capability(A Rms)AC33 380V
200 400 630 800 1000 1250 1250
Rated short-current making capability lcm(kA peak value)
8 8 10 10 10 12 12
Mechanical durability(number of cyclic operation)
8000 8000 8000 8000 8000 5000 5000
Electric durability
COSØ=0.65 AC33
1500 1500 1500 1500 1500 1000 1000
Change-oner time
I-0-II or II-0-1(s)
0.5 0.5 0.5 0.5 0.5 1.0 1.0
I-0 or II-0(s)
0.3 0.3 0.3 0.3 0.3 0.6 0.6
Power consumption of electrical control
24V(DC)(w)
50 50 50 50 50 75 75
220V(AC)(w)
50 50 50 50 50 75 75
Moment of operation(Nm)
15 15 15 15 15 22 22
Weight(kg)
3 Poles
8.2 8.2
4 Poles
4.2 4.3 4.4 4.5 4.5 8.7 8.7

 

 

  Back